Description
KENJING’s KJSF6-12 SF6 gas-insulated switchgear is a modular ring main unit platform for medium-voltage distribution. A sealed gas tank (IP67) integrates the vacuum circuit breaker, three-position isolator/earthing switch, CT/PT, surge arresters, and plug-in bushings. Single-tank or common-tank lineups adapt to incoming, feeder, and PT units with side or top extensions, enabling compact two-in/two-out and two-in/four-out schemes for urban networks, industrial plants, and renewables.
Key Features and Advantages
Sealed, compact architecture
Gas-insulated compartment with robotic welds; enclosure protection up to IP4X and gas tank IP67. Typical tank pressure 0.04–0.05 MPa; annual leakage rate < 0.01%. Cabinet width can be as low as ~325 mm for high feeder density.Flexible modules
PT cabinet, V-cabinet (VCB + isolator), and common-tank VVV options. Standard 630 A busbar/feeder rating, with short-time withstand 20 kA/4 s or 25 kA/4 s and peak 50/63 kA. Supports loop switching, transformer and cable-charging duties.High insulation strength
Power-frequency withstand and lightning impulse levels meet international RMU practice (e.g., 12/18/24 kV classes with typical 42/48–50/65 kV PF and 75/85–125/145 kV LI values across phase-to-phase, phase-to-earth, and open-gap).Safety interlocking
Five-interlock logic between the breaker, isolator/earthing switch and doors prevents mis-operation. Pressure gauge and inspection window enable safe condition checks.Fast fault clearing
Vacuum circuit breaker with spring operating mechanism delivers high making/breaking capability and long mechanical life (up to 10,000 operations). Optional F-unit combines load switch + fuse for transformer protection.Digital-ready
Optional DTU integrates measurement, control and protection; supports feeder automation and remote SCADA.Standards compliance
Designed around IEC 56/62271-100 (circuit-breakers), IEC 129/62271-102 (isolating & earthing switches), IEC 298/62271-200 (metal-enclosed switchgear), IEC 60529 (IP), and related CT/PT standards.
Typical Applications
Urban distribution RMUs, industrial substations, renewable collection points, compact secondary substations, and network automation retrofits.
Ordering Information (what to specify)
Rated voltage, rated current, and short-circuit breaking / withstand levels.
Function per panel: load switch or circuit breaker (VCB).
Isolator arrangement: upper- or lower-isolation type.
Mechanism supply (AC/DC 220/110/48/24 V), secondary wiring, and special interlocks.
Busbars, incoming/outgoing plug-in bushings, and side/top extensions.
Why Choose KENJING
Proven sealed-tank engineering for long service intervals and environmental robustness.
Configurable RMU platform that scales from single-tank PT and feeder panels to common-tank multi-feeder solutions.
Production quality with robotic welding, tight leak-rate control, and full routine tests to IEC.
Lifecycle support — engineering assistance, spares, and retrofit guidance for network upgrades.
Upgrade your MV distribution with a compact, safe SF6 gas-insulated switchgear lineup. Send your single-line and required ratings to KENJING for a fast configuration and quote.
| NO. | Item | Unit | Parameter | ||
| 1 | Rated Voltage | kV | 12 | 18 | 24 |
| 2 | Rated Frequency | Hz | 50/60 | ||
| 3 | Rated Current | A | 630 | ||
| 4 | Rated Short-Time Withstand Current | kA/s | 20/4 25/4 | ||
| 5 | Rated Peak Withstand Current | kA | 50 63 | ||
| 6 | Rated Power-Frequency Withstand Voltage(phase-to-phase, phase-to-earth/ across isolating distance) | kV | 42/48 | 50/55 | 50/65 |
| 7 | Rated Lightning Impulse Withstand Voltage(phase-to-phase, phase-to-earth/ across isolating distance) | kV | 75/85 | 88/100 | 125/145 |
| 8 | Rated Short-Circuit Breaking Current | kA | 20 25 | ||
| 9 | Rated Short-Circuit Making Current | kA | 50 63 | ||
| 10 | Partial Discharge | PC | ≤ 20 | ||
| 11 | Temperature Rise | K | ≤ 65 | ||
| 12 | Mechanical Life(isolation switch, earthing switch/ circuit-breaker) | time | 3000/10000 | ||
| 13 | Main Circuit Resistance | μΩ | ≤ 150 | ||
| 14 | Degree of Protection(Gas Tank / Enclosure) | IP67/1P4X | |||
| 15 | Rated Filling Pressure(gauge pressure at 20°C) | MPa | 0.04-0.05 | ||