GIS

KENJING SF6 Gas-Insulated Switchgear (RMU) — Modular, Sealed Medium-Voltage Distribution

Modular SF6 gas-insulated switchgear (RMU) with sealed IP67 tank, vacuum circuit breaker, and three-position isolator. Single- or common-tank panels (630 A, up to 25 kA/4 s) build two-in/two-out or two-in/four-out schemes with DTU-ready automation.

Description

KENJING’s KJSF6-12 SF6 gas-insulated switchgear is a modular ring main unit platform for medium-voltage distribution. A sealed gas tank (IP67) integrates the vacuum circuit breaker, three-position isolator/earthing switch, CT/PT, surge arresters, and plug-in bushings. Single-tank or common-tank lineups adapt to incoming, feeder, and PT units with side or top extensions, enabling compact two-in/two-out and two-in/four-out schemes for urban networks, industrial plants, and renewables.

Key Features and Advantages

  • Sealed, compact architecture
    Gas-insulated compartment with robotic welds; enclosure protection up to IP4X and gas tank IP67. Typical tank pressure 0.04–0.05 MPa; annual leakage rate < 0.01%. Cabinet width can be as low as ~325 mm for high feeder density.

  • Flexible modules
    PT cabinet, V-cabinet (VCB + isolator), and common-tank VVV options. Standard 630 A busbar/feeder rating, with short-time withstand 20 kA/4 s or 25 kA/4 s and peak 50/63 kA. Supports loop switching, transformer and cable-charging duties.

  • High insulation strength
    Power-frequency withstand and lightning impulse levels meet international RMU practice (e.g., 12/18/24 kV classes with typical 42/48–50/65 kV PF and 75/85–125/145 kV LI values across phase-to-phase, phase-to-earth, and open-gap).

  • Safety interlocking
    Five-interlock logic between the breaker, isolator/earthing switch and doors prevents mis-operation. Pressure gauge and inspection window enable safe condition checks.

  • Fast fault clearing
    Vacuum circuit breaker with spring operating mechanism delivers high making/breaking capability and long mechanical life (up to 10,000 operations). Optional F-unit combines load switch + fuse for transformer protection.

  • Digital-ready
    Optional DTU integrates measurement, control and protection; supports feeder automation and remote SCADA.

  • Standards compliance
    Designed around IEC 56/62271-100 (circuit-breakers), IEC 129/62271-102 (isolating & earthing switches), IEC 298/62271-200 (metal-enclosed switchgear), IEC 60529 (IP), and related CT/PT standards.

Typical Applications

Urban distribution RMUs, industrial substations, renewable collection points, compact secondary substations, and network automation retrofits.

Ordering Information (what to specify)

  1. Rated voltage, rated current, and short-circuit breaking / withstand levels.

  2. Function per panel: load switch or circuit breaker (VCB).

  3. Isolator arrangement: upper- or lower-isolation type.

  4. Mechanism supply (AC/DC 220/110/48/24 V), secondary wiring, and special interlocks.

  5. Busbars, incoming/outgoing plug-in bushings, and side/top extensions.


Why Choose KENJING

  • Proven sealed-tank engineering for long service intervals and environmental robustness.

  • Configurable RMU platform that scales from single-tank PT and feeder panels to common-tank multi-feeder solutions.

  • Production quality with robotic welding, tight leak-rate control, and full routine tests to IEC.

  • Lifecycle support — engineering assistance, spares, and retrofit guidance for network upgrades.

Upgrade your MV distribution with a compact, safe SF6 gas-insulated switchgear lineup. Send your single-line and required ratings to KENJING for a fast configuration and quote.

NO.ItemUnitParameter
1Rated VoltagekV121824
2Rated FrequencyHz50/60
3Rated CurrentA630
4Rated Short-Time Withstand CurrentkA/s20/4 25/4
5Rated Peak Withstand CurrentkA50 63
6Rated Power-Frequency Withstand Voltage(phase-to-phase, phase-to-earth/ across isolating distance)kV42/4850/5550/65
7Rated Lightning Impulse Withstand Voltage(phase-to-phase,
phase-to-earth/ across isolating distance)
kV75/8588/100125/145
8Rated Short-Circuit Breaking CurrentkA20 25
9Rated Short-Circuit Making CurrentkA50 63
10Partial DischargePC≤ 20
11Temperature RiseK≤ 65
12Mechanical Life(isolation switch, earthing switch/
circuit-breaker)
time3000/10000
13Main Circuit ResistanceμΩ≤ 150
14Degree of Protection(Gas Tank / Enclosure)IP67/1P4X
15Rated Filling Pressure(gauge pressure at 20°C)MPa0.04-0.05

RMU-5