Description
The GKJ C-GIS series is a compact, metal-enclosed medium-voltage switchgear that uses SF₆ (or dry air/N₂ on request) as the primary insulating medium inside a stainless-steel, hermetically sealed tank. It is engineered for three-phase AC distribution and section-alizing systems in transmission and substations, industrial/mining facilities, rail transit, renewable plants, and dense urban networks—especially where humidity, dust, altitude, or pollution demand IP-rated, corrosion-resistant equipment.
A horizontally arranged VKJY vacuum circuit breaker (VCB) is integrated as the main switching device. A mechanically linked three-position switch (Close–Open–Earth) provides make/isolate/earthing in one unit, simplifying primary layouts and improving interlocking safety. The intelligent control module monitors breaker status, three-position switch position, gas pressure, and spring energy storage; it also acquires voltage/current/energy/frequency, logs faults, and supports conventional secondary control for streamlined on-site commissioning.
Model Meaning
GKJ – □ / □ – □
- Rated short-circuit breaking current (kA)
- Rated current (A)
- Rated voltage (kV)
- Company gas-insulated switchgear model code
Conditions of Use
- Ambient temperature: −25 °C…+40 °C
- Altitude: ≤ 1000 m (consult for > 4000 m)
- Humidity: daily avg ≤ 95 %; monthly avg ≤ 90 % (water-vapor pressure daily ≤ 2.2 kPa; monthly ≤ 1.8 kPa)
- Environment: clean, non-flammable, minimal dust/smoke/salt spray; free of severe vibration; EMC induced voltage in secondary ≤ 1.6 kV; seismic intensity ≤ 8°
Reference Standards
GB/T 3906, GB/T 11022, DL/T 593, GB/T 404; GB/T 1984 (AC circuit-breakers); GB/T 3804 (AC load-break switches & earthing); plus related IEC-aligned specifications for GIS assemblies.
Product Features
- Integrated breaker & three-position switch: One sealed tank delivers Close–Open–Earth with direct mechanical interlock for dependable “Five-Protection” compliance.
- High dielectric & arc safety: Vacuum interruption with SF₆ (or dry gas) insulation; internal arc design tested up to 40 kA/1 s.
- Smart monitoring: Gas density/pressure indication, energy-storage status, position sensing, measurement & fault recording for quick diagnostics.
- Corrosion-resistant build: Stainless enclosure, nickel/zinc-plated mechanisms; high salt-spray endurance.
- Low-leakage, high IP: ≤ 0.01 %/y leakage; IP68 tank prevents moisture ingress for tropical/condensing sites.
- Fast installation: Pre-assembled modules on a common aluminum plate; minimal field adjustment; simplified secondary wiring.
- Efficient conductors: T2 silver-plated copper main circuits meet 1.1× rated temperature-rise requirements.
Switches & Mechanisms (Core Components)
VKJX-12…40.5 Vacuum Circuit Breaker
- Rated voltage: 12/24/40.5 kV; rated current: 630…3150 A
- Short-circuit breaking: 25/31.5/40 kA (12 kV) or 20/25/31.5 kA (24/40.5 kV)
- Short-time withstand: 25/31.5/40 kA for 4 s; Making (peak): 63/80/100 or 50/63/80 kA
- Control: Closing/opening coils DC 220 V (typ.), 1.3 A; energy-storage motor 120 W, DC 220 V
- Timing: Opening 20 ≤ t ≤ 50 ms; Closing 30 ≤ t ≤ 70 ms; contact bounce ≤ 2 ms; PD ≤ 10 pC
- Mechanical life: E2 duty; numerous rated fault operations
SKJY-12…40.5 Three-Position Disconnector/Earthing Switch
- Power-frequency withstand (1 min): 42/65/95 kV (phase-to-phase/earth), 48/79/118 kV (across gap)
- Lightning impulse: 75/125/185 kV (phase-to-phase/earth), 85/145/215 kV (across gap)
- Manual operating torque: 200 N·m; mechanical life: 3000 ops
- Motorized drive: 200 W, DC 220 V/110 V; operating range 85%–110%
Typical Schemes
Cable incoming/outgoing; Incoming with PT; Overhead line incoming; Sectionalizer with circuit breaker; Sectionalizing isolator; Stand-alone PT unit. Single- or double-gas-compartment layouts are available to match feeder counts and footprint.
Ordering Information
When requesting GKJ C-GIS, please specify:
- Rated voltage, rated current, and short-circuit breaking current;
- Scheme type (e.g., incoming feeder, outgoing feeder, PT, sectionalizer), single-line diagram, arrangement, and quantity;
- Secondary wiring diagram/terminal plan (or use factory standard);
- Auxiliary/control power supply and optional accessories;
- Gas type (SF₆ / dry air / N₂), altitude/special environment if applicable;
- Required spare parts and any non-standard features.
Why GKJ C-GIS
Compact, internally arc-safe construction; robust mechanical interlocks; intelligent diagnostics; and wide ratings up to 40.5 kV/3150 A make GKJ C-GIS an excellent choice for modern MV networks where reliability, safety, and rapid deployment matter.
| NO. | Model | Unit | Rating | |||
| 1 | Rated Voltage | kV | 12 | 24 | 40.5 | |
| 2 | Rated Frequency | Hz | 50 | |||
| 3 | Rated Current | A | 630~3150 | |||
| 4 | Rated Short-time Power-frequency Withstand Voltage(1 min,RMS,zero phase) | Phase-to-earth and phase-to-phase | kV | 42 | 65 | 95 |
| Across isolating distance | kV | 48 | 79 | 118 | ||
| Auxiliary and control circuits | kV | 2 | ||||
| 5 | Rated Lightning Impulse Withstand Voltage(Peak,zero phase) | Phase-to-earth and phase-to-phase | kV | 75 | 125 | 185 |
| Across isolating distance | kV | 85 | 145 | 215 | ||
| 6 | Rated Short-circuit Breaking Current | kA | 25/31.5/40 | 20/25/31.5 | 20/25/31.5 | |
| 7 | Rated Short-circuit Making Current(Peak) | kA | 63/80/100 | 50/63/80 | 50/63/80 | |
| 8 | Number of Rated Short-circuit Breakings | Time | 30(E2 level) | |||
| 9 | Rated Short-time Withstand Current of Main Circuit and Earthing Switch | kA/s | 25/4,31.5/4,40/4 | |||
| 10 | Rated Peak Withstand Current of Main Circuit and Earthing Switch | kA | 63,80,100 | |||
| 11 | Partial Discharge of Complete Switchgear | pC | ≤ 20 | |||
| 12 | Annual Gas Leakage Rate | %/Y | ≤ 0.01 | |||
| 13 | Annual Gas Leakage Rate | μL/L | <1000 | |||
| 14 | Rated Operating Sequence | 0-0.3s-CO-180s-CO | ||||
| 15 | Insulating Gas | N2 / dry air / SF6 | ||||
| 16 | Rated Gas Pressure(Relative Pressure, 20°C) | MPa | 0.03 | |||
| 17 | Design Pressure(Relative Pressure, 20°C) | MPa | 0.07 | |||
| 18 | Alarm Pressure(Relative Pressure,20°C) | MPa | 0.01 | |||
| 19 | Minimum Insulation Pressure(Relative Pressure,20°C) | MPa | 0 | |||
| 20 | Internal Arc Rating | kA | IAC | |||
| 21 | Internal Arc Rating | kA/s | 25/1,31.5/1,40/1 | |||
| 22 | Accessible Part Classification | / | A(F,L,R) | |||
| 23 | Loss of Service Continuity Level | / | LSC2A | |||
| 24 | Protection Degree | Protection Degree | / | IP68 | ||
| Cabinet Enclosure | / | IP41 | ||||
| 25 | Circuit Resistance | μΩ | ≤ 80(630A) ≤ 75(1250A)≤65(1600~2000A)≤60(2500及以上) | |||
| 26 | Rated Voltage of Auxiliary Circuits | V | AC/DC220 | |||
| 27 | Overall Dimensions(W x D x H,excluding cabinet door) | mm | 500x1100x2400(630A~1250A) | |||
| 600x1100x2400(630AV1250A) | ||||||
| 800~1000×1550/1650×2400(1600A~3150A) | ||||||
| Note: Cabinet dimensions are negotiable. | ||||||