GKJ 40

KENJING GKJ C-GIS Gas-Insulated Metal-Enclosed Switchgear — Compact, Arc-safe MV Distribution up to 40.5 kV

Compact metal-enclosed GIS for medium voltage networks, integrating a vacuum circuit breaker and three-position switch in a sealed tank. Delivers high dielectric strength, internal-arc safety, low leakage and fast installation for substations, renewables, rail and industrial loads.

Description

The GKJ C-GIS series is a compact, metal-enclosed medium-voltage switchgear that uses SF₆ (or dry air/N₂ on request) as the primary insulating medium inside a stainless-steel, hermetically sealed tank. It is engineered for three-phase AC distribution and section-alizing systems in transmission and substations, industrial/mining facilities, rail transit, renewable plants, and dense urban networks—especially where humidity, dust, altitude, or pollution demand IP-rated, corrosion-resistant equipment.

A horizontally arranged VKJY vacuum circuit breaker (VCB) is integrated as the main switching device. A mechanically linked three-position switch (Close–Open–Earth) provides make/isolate/earthing in one unit, simplifying primary layouts and improving interlocking safety. The intelligent control module monitors breaker status, three-position switch position, gas pressure, and spring energy storage; it also acquires voltage/current/energy/frequency, logs faults, and supports conventional secondary control for streamlined on-site commissioning.

Model Meaning

GKJ – □ / □ – □

  • Rated short-circuit breaking current (kA)
  • Rated current (A)
  • Rated voltage (kV)
  • Company gas-insulated switchgear model code

Conditions of Use

  • Ambient temperature: −25 °C…+40 °C
  • Altitude: ≤ 1000 m (consult for > 4000 m)
  • Humidity: daily avg ≤ 95 %; monthly avg ≤ 90 % (water-vapor pressure daily ≤ 2.2 kPa; monthly ≤ 1.8 kPa)
  • Environment: clean, non-flammable, minimal dust/smoke/salt spray; free of severe vibration; EMC induced voltage in secondary ≤ 1.6 kV; seismic intensity ≤ 8°

Reference Standards

GB/T 3906, GB/T 11022, DL/T 593, GB/T 404; GB/T 1984 (AC circuit-breakers); GB/T 3804 (AC load-break switches & earthing); plus related IEC-aligned specifications for GIS assemblies.

Product Features

  • Integrated breaker & three-position switch: One sealed tank delivers Close–Open–Earth with direct mechanical interlock for dependable “Five-Protection” compliance.
  • High dielectric & arc safety: Vacuum interruption with SF₆ (or dry gas) insulation; internal arc design tested up to 40 kA/1 s.
  • Smart monitoring: Gas density/pressure indication, energy-storage status, position sensing, measurement & fault recording for quick diagnostics.
  • Corrosion-resistant build: Stainless enclosure, nickel/zinc-plated mechanisms; high salt-spray endurance.
  • Low-leakage, high IP: ≤ 0.01 %/y leakage; IP68 tank prevents moisture ingress for tropical/condensing sites.
  • Fast installation: Pre-assembled modules on a common aluminum plate; minimal field adjustment; simplified secondary wiring.
  • Efficient conductors: T2 silver-plated copper main circuits meet 1.1× rated temperature-rise requirements.

Switches & Mechanisms (Core Components)

VKJX-12…40.5 Vacuum Circuit Breaker

  • Rated voltage: 12/24/40.5 kV; rated current: 630…3150 A
  • Short-circuit breaking: 25/31.5/40 kA (12 kV) or 20/25/31.5 kA (24/40.5 kV)
  • Short-time withstand: 25/31.5/40 kA for 4 s; Making (peak): 63/80/100 or 50/63/80 kA
  • Control: Closing/opening coils DC 220 V (typ.), 1.3 A; energy-storage motor 120 W, DC 220 V
  • Timing: Opening 20 ≤ t ≤ 50 ms; Closing 30 ≤ t ≤ 70 ms; contact bounce ≤ 2 ms; PD ≤ 10 pC
  • Mechanical life: E2 duty; numerous rated fault operations

SKJY-12…40.5 Three-Position Disconnector/Earthing Switch

  • Power-frequency withstand (1 min): 42/65/95 kV (phase-to-phase/earth), 48/79/118 kV (across gap)
  • Lightning impulse: 75/125/185 kV (phase-to-phase/earth), 85/145/215 kV (across gap)
  • Manual operating torque: 200 N·m; mechanical life: 3000 ops
  • Motorized drive: 200 W, DC 220 V/110 V; operating range 85%–110%

Typical Schemes

Cable incoming/outgoing; Incoming with PT; Overhead line incoming; Sectionalizer with circuit breaker; Sectionalizing isolator; Stand-alone PT unit. Single- or double-gas-compartment layouts are available to match feeder counts and footprint.

Ordering Information

When requesting GKJ C-GIS, please specify:

  • Rated voltage, rated current, and short-circuit breaking current;
  • Scheme type (e.g., incoming feeder, outgoing feeder, PT, sectionalizer), single-line diagram, arrangement, and quantity;
  • Secondary wiring diagram/terminal plan (or use factory standard);
  • Auxiliary/control power supply and optional accessories;
  • Gas type (SF₆ / dry air / N₂), altitude/special environment if applicable;
  • Required spare parts and any non-standard features.

Why GKJ C-GIS
Compact, internally arc-safe construction; robust mechanical interlocks; intelligent diagnostics; and wide ratings up to 40.5 kV/3150 A make GKJ C-GIS an excellent choice for modern MV networks where reliability, safety, and rapid deployment matter.

NO.ModelUnitRating
1Rated VoltagekV122440.5
2Rated FrequencyHz50
3Rated CurrentA630~3150
4Rated Short-time Power-frequency Withstand
Voltage(1 min,RMS,zero
phase)
Phase-to-earth and phase-to-phasekV426595
Across isolating distancekV4879118
Auxiliary and control circuitskV2
5Rated Lightning
Impulse Withstand
Voltage(Peak,zero phase)
Phase-to-earth and phase-to-phasekV75125185
Across isolating distancekV85145215
6Rated Short-circuit Breaking CurrentkA25/31.5/4020/25/31.520/25/31.5
7Rated Short-circuit Making Current(Peak)kA63/80/10050/63/8050/63/80
8Number of Rated Short-circuit BreakingsTime30(E2 level)
9Rated Short-time Withstand Current of Main Circuit and Earthing SwitchkA/s25/4,31.5/4,40/4
10Rated Peak Withstand Current of Main Circuit and Earthing SwitchkA63,80,100
11Partial Discharge of Complete SwitchgearpC≤ 20
12Annual Gas Leakage Rate%/Y≤ 0.01
13Annual Gas Leakage RateμL/L<1000
14Rated Operating Sequence0-0.3s-CO-180s-CO
15Insulating GasN2 / dry air / SF6
16Rated Gas Pressure(Relative Pressure, 20°C)MPa0.03
17Design Pressure(Relative Pressure, 20°C)MPa0.07
18Alarm Pressure(Relative Pressure,20°C)MPa0.01
19Minimum Insulation Pressure(Relative Pressure,20°C)MPa0
20Internal Arc RatingkAIAC
21Internal Arc RatingkA/s25/1,31.5/1,40/1
22Accessible Part Classification/A(F,L,R)
23Loss of Service Continuity Level/LSC2A
24Protection DegreeProtection Degree/IP68
Cabinet Enclosure/IP41
25Circuit ResistanceμΩ≤ 80(630A) ≤ 75(1250A)≤65(1600~2000A)≤60(2500及以上)
26Rated Voltage of Auxiliary CircuitsVAC/DC220
27Overall Dimensions(W x D x H,excluding cabinet door)mm500x1100x2400(630A~1250A)
600x1100x2400(630AV1250A)
800~1000×1550/1650×2400(1600A~3150A)
Note: Cabinet dimensions are negotiable.