switchgear

KENJING DFW-12 High-Voltage Cable Branch Box — Pad Mounted Switchgear

Outdoor pad mounted switchgear cable branch box with 25 kA breaking, 63 kA peak making, AC220 V control power, high-speed I/O, and IEC 60870-5-101/104 communications—built for reliable MV loop and underground distribution networks.

The KENJING DFW-12 is outdoor pad mounted switchgear engineered for medium-voltage loop and radial networks. It integrates metering, protection I/O, fast communications, and arc-resistant primary switching in a compact pad mounted switchgear enclosure. With utility-grade EMC (DL/T 721-2013 Level IV), wide-range auxiliary supply, and mechanical life to 10,000 operations, it suits feeders, industrial plants, renewables tie-ins, and underground distribution switchgear projects.

Key Features and Advantages

  • Primary performance (MV): short-circuit breaking 25 kA, making 63 kA (peak), short-time withstand 25 kA; typical continuous current up to 630 A—aligned with pad mounted switchgear feeder duties.

  • High-speed protection I/O: contact inputs (DC24 V) with ≤2 ms response; two relay output groups (AC250 V/16 A; DC48 V/10 A; DC30 V/16 A) for tripping, interlocks, or transfer on pad mounted switchgear schemes.

  • Accurate measurement: current 0–100 A range; accuracy U: 0.5%, Q: 1%, f: 0.01 Hz—supports fault location and load studies within pad mounted switchgear assets.

  • Robust control power: AC220 V ±20%, 50 Hz; total consumption ≤15 VA for efficient pad mounted switchgear auxiliary design.

  • Comms for SCADA/DMS: 4× RS-232/RS-485 and 2× 10/100M Ethernet; IEC 60870-5-101/104 for easy substation and feeder automation across pad mounted switchgear fleets.

  • Environmental resilience: −40 to +70 °C, ≤95% RH (no condensation); three-phase operation asynchronism ≤2 ms—stable in harsh pad mounted switchgear environments.

  • Long life, low OPEX: 30 fault O-C duties at rating; mechanical life 10,000—ideal for pad mounted switchgear in ring and spur applications.

  • Compatible topologies: works as cable branch box, RMU node, or sectionalizing point within pad mounted switchgear networks.

Why Choose Us (KENJING)

  • Engineer-focused delivery: application sizing, protection coordination, and wiring diagrams optimized for pad mounted switchgear deployments.

  • Proven reliability: type-tested assemblies and documented QA; fast spares and lifecycle support across pad mounted switchgear installations.

  • Integration ready: pre-configured protocols and I/O mapping reduce commissioning time for pad mounted switchgear and ring main unit (RMU) sites.

Upgrade your feeder reliability with KENJING pad mounted switchgear. Send your single-line diagram and duty requirements—our engineers will return a matched DFW-12 configuration, drawings, and delivery plan.

ItemParameters
Operating Power SupplyControl terminal part: AC220V ± 20%, 50Hz
Total Power Consumption≤ 15VA
Operating EnvironmentOperating temperature: -40~70°C
Operating humidity: ≤ 95%, no condensation
Measurement InputMeasurable range: Voltage: 0100A
Accuracy: U: 0.5%; Q: 1%; f: 0.01Hz
Signal InputContact signal: DC24V
Response time: ≤ 2ms
Signal OutputStandard configuration: 2 groups
Output method: Power relays
Contact capacity: AC250V/16A; DC48V/10A; DC30V/16A
Communication MethodStandard configuration: 4 RS232/RS485 ports, 2 10/100M Ethernet ports
Protocols: Support IEC60870-5-101, IEC60870-5-104 and equivalent standards
Electromagnetic CompatibilityComplies with DL/T 721-2013 Power Industry Standard IV level
Primary Switch ParametersRated short-circuit breaking current: 25kA
Rated continuous current: 63kA
Rated short-circuit withstand current (peak): 25kA
Rated short-circuit making current (peak): 63kA
Rated short-circuit breaking current opening-closing frequency: 30 times
Mechanical Life10,000 times
Three-Phase Operation Asynchronism≤ 2ms

jiubabege

Contact Us

Related Products