swichgear-4

KENJING Eco-friendly Gas Insulated Metal Enclosed Switchgear | RMU Series

KENJING eco-friendly gas insulated switchgear is a compact RMU for 12–24 kV networks. It integrates a vacuum circuit breaker, three-position isolator, IP67 gas tank, and DTU-ready automation with 630 A feeders and 20–25 kA/4 s fault performance for safe, reliable MV distribution

Description

KENJING’s eco-friendly gas insulated switchgear (KJHB-12/18/24, 630 A) is a compact ring main unit (RMU) platform for utility and industrial MV networks. Single-tank or common-tank designs integrate isolators and vacuum circuit breaker protection in IP67/IP4X sealed enclosures—engineered for safety, uptime, and fast project delivery.

Key Features

  • Ratings: 12, 18, 24 kV classes, 50/60 Hz, 630 A bus/circuit. Short-time 20–25 kA/4 s, peak 50/63 kA.

  • Dielectric: PF withstand (phase-phase/phase-earth/isolating gap) up to 42/48/65/79 kV by class; LIWV up to 75/85/125/145 kV; partial discharge ≤ 20 pC.

  • Sealing & Protection: IP67 gas tank / IP4X enclosure; fill pressure ≈ 0.02 MPa at 20 °C; annual leakage ≤ 0.01%.

  • Cabinet Options:

    • PT cabinet (single-tank): VT/CT metering, surge protection, copper bus, tap-off ready.

    • VCB cabinet (single-tank): three-position isolating grounding switch + VCB with five-interlock logic, gauge, and sight window.

    • VVV cabinet (common-tank): multi-feeder shared-tank layout for dense footprints.

  • Endurance & Losses: mechanical life up to 10,000 ops (CB), ≤ 150 µΩ loop resistance.

  • Automation-Ready: optional DTU for measurement, control, protection, and comms.

  • Layouts: side/top bus extensions; standardized two-in/two-out and two-in/four-out outdoor plans.

Typical Applications

Urban distribution kiosks, compact substations, industrial feeders, renewable tie-ins, RMU retrofits requiring reliable medium voltage switchgear with minimal footprint.

Standards & Compliance

Designed to IEC 56, 129, 137, 44-1, 255, 265-1, 62271 series, 298, 439, 694; enclosure protection to IEC 60529; corrosion protection to ISO 2063.

Ordering Checklist

  1. Rated voltage/current and fault level.

  2. Switch type: isolator or circuit breaker; upper/lower isolation for CB.

  3. Insulation: semi-solid or fully solid options.

  4. Mechanism supply and secondary wiring scope.

  5. Copper bars, in/out bushings, and side/top extensions required.

  6. Drawings: single-line, protection settings, and panel arrangement.

Why Choose KENJING

  • Reduced risk: sealed compartments and interlocked operations protect personnel and assets.

  • Project speed: modular bays and standard plans shorten engineering and installation.

  • Operational uptime: robust dielectric margins, IP67 gas tank, and DTU diagnostics.

  • Lifecycle value: low leakage, low resistance, and high mechanical life lower total cost.

Upgrade your network with compact, automation-ready gas insulated switchgear from KENJING. Share your single-line and fault levels—we’ll return a matched PT/VCB/VVV configuration, GA drawings, and a firm lead time.

NO.ItemUnitParameter
1Rated VoltagekV121824
2Rated FrequencyHz50/60
3Rated CurrentA630
4Rated Short-Time Withstand CurrentkA/s20/4 25/4
5Rated Peak Withstand CurrentkA50 63
6Rated Power-Frequency Withstand Voltage(phase-to-phase, phase-to-earth/ across isolating distance)kV42/4850/5550/65
7Rated Lightning Impulse Withstand Voltage(phase-to-phase, phase-to-earth/ across isolating distance)kV75/8588/100125/145
8Rated Short-Circuit Breaking CurrentkA20 25
9Rated Short-Circuit Making CurrentkA50 63
10Partial DischargePC≤ 20
11Temperature RiseK≤ 65
12Mechanical Life(isolation switch, earthing switch/
circuit-breaker)
time3000/10000
13Loop Resistance(Main Circuit Resistance)μΩ≤ 150
14Degree of Protection(Enclosure / Gas Tank)IP67/1P4X
15Rated Filling Pressure(gauge pressure at 20°C)MPa0.02
16Annual Leakage Rate%≤ 0.01

ayeiad

Contact Us

Related Products

Contact Us