The KENJING SF6 Vacuum Circuit Breaker Switch is a vacuum circuit breaker built for dependable MV fault clearing at 24 kV. It combines a sealed SF₆-insulated pole with a vacuum interrupter to deliver fast arc extinction, high dielectric strength, and low maintenance. This medium voltage vacuum circuit breaker suits RMUs, metal-enclosed switchgear, feeders, and transformer incomers requiring compact design and proven reliability under repetitive duty.
Key Features and Advantages
Primary ratings: 24 kV, 630 A vacuum circuit breaker with ≤ 60 µΩ main-circuit resistance for low thermal rise and efficient conduction.
Interrupting & withstand: Rated breaking current 20 kA (4 s thermal stability); short-circuit making/peak 50/63 kA, 30 making operations—robust electrodynamic strength for bus ties and transformer feeders.
Dielectric performance: Power-frequency withstand 65 kV (phase-ground/phase-phase), 79 kV (open contact); lightning impulse 125 kV (phase-ground/phase-phase), 145 kV (open contact)—secure insulation margins for MV systems.
Endurance: 10,000 operations for the arc-chamber mechanism; 5,000 for the isolation/grounding switch—ideal for networks where the vacuum circuit breaker sees frequent switching.
Application fit: Optimized for GIS/RMU and indoor metal-enclosed assemblies; accessory options include motor charging, anti-pump, aux contacts, mechanical/electrical interlocks, and protection relay interfaces to finalize your vacuum circuit breaker specifications.
Safety & maintenance: Vacuum interruption eliminates decomposition by-products; sealed SF₆ housing improves ingress protection and service life while keeping the vacuum circuit breaker footprint compact.
Why Choose Us (KENJING)
Engineer-led sizing: Our power engineers configure the vacuum circuit breaker to your fault levels, protection settings, and coordination study.
Quality assurance: Each vacuum circuit breaker undergoes routine dielectric, timing, and mechanical tests with full traceability.
Lifecycle support: Spares, retrofit kits, FAT/SAT assistance, and documentation ensure your vacuum circuit breaker fleet runs reliably with predictable maintenance.
Specify a KENJING vacuum circuit breaker with confidence. Send your single-line and protection requirements, and our team will return drawings, pricing, and delivery for a 24 kV medium voltage vacuum circuit breaker that matches your project.
NO | ITEM | UNIT | PARAMETERS | REMARKS |
1 | Rated Frequency | kV | 24 | |
2 | Rated Current | A | 630 | |
3 | Rated Breaking Current/Time to Thermal Stability | kA/s | 20/4 | |
4 | Rated Peak Withstand Current | kA | 50/63 | |
5 | Rated Short-Circuit Making Current | kA | 50/63 | |
6 | Short-Circuit Making Times | 次 | 30 | |
7 | Power Frequency Withstand Voltage: Phase-to-Ground Phase-to-Phase | kV | 65 | |
8 | Power Frequency Withstand Voltage: Open Contact | kV | 79 | |
9 | Lightning Impulse Withstand Voltage: Phase-to-Ground Phase-to-Phase | kV | 125 | |
10 | Lightning Impulse Withstand Voltage: Open Contact | kV | 145 | |
11 | Main Circuit Resistance | μΩ | ≤60 | |
12 | Arc Extinguishing Chamber Mechanical Life | TIME | 10000 | |
13 | Isolation/Grounding Switch Mechanical Life | TIME | 5000 |