The KENJING Isolation Circuit Breaker Switch integrates a vacuum circuit breaker inside a sealed environmental protection cabinet to deliver dependable medium-voltage switching and isolation for distribution feeders, RMUs, and compact substations. Optimized for 12 kV networks and 630 A feeders, this vacuum circuit breaker achieves 20/4 kA or 25/3 kA thermal stability, 50/63 kA making, and 10,000 mechanical operations. With 42/48 kV power-frequency and 75/85 kV impulse withstand levels, low ≤60 µΩ main circuit resistance, and a 1.25 bar gas box, the vacuum circuit breaker maintains low losses and high dielectric margins. Ideal where compact, sealed, medium voltage vacuum circuit breaker solutions are required.
Key Features and Advantages
MV performance, compact footprint – 12 kV class, 630 A rated vacuum circuit breaker for feeder protection and sectionalizing in RMUs/cabinets.
Fault duty – Rated breaking/thermal stability: 20 kA/4 s or 25 kA/3 s; rated short-circuit making 50/63 kA; peak withstand 50/63 kA; supports 30 short-circuit closing operations.
Dielectric strength – Power-frequency withstand 42 kV (to ground/phase-phase) / 48 kV (across contacts); lightning impulse 75/85 kV for overvoltage resilience.
Endurance – 10,000 operations (arc-chamber); 5,000 operations (isolating/earthing); engineered for low maintenance vacuum circuit breaker service.
Low resistance path – ≤ 60 µΩ main circuit resistance reduces I²R losses and heating.
Environmental protection cabinet – 1.25 bar gas box; sealed design enhances reliability in dust, humidity, and corrosive atmospheres; pairs perfectly with 12kV vacuum circuit breaker applications.
Operator safety & selectivity – Independent isolation/earthing functions, clear operation sequences, and predictable vacuum circuit breaker interruption.
Why Choose Us (KENJING)
Engineer-led designs focused on grid code compliance and lifecycle cost.
Type-tested assemblies with documented dielectric and short-circuit performance.
Responsive customization for control schemes, interlocks, CT/VT options, and communication interfaces.
Global support – application sizing, commissioning guidance, and spares throughout service life.
Upgrade feeder reliability with a sealed vacuum circuit breaker cabinet engineered for endurance and safety. Contact KENJING for drawings, pricing, and lead time, or request a configuration matched to your protection scheme.
NO | ITEM | UNIT | PARAMETERS | REMARKS |
1 | Rated Voltage | kV | 12 | |
2 | Rated Current | A | 630 | |
3 | Rated Breaking Current / Thermal Stability Time | kA/s | 20/4 ;25/3 | |
4 | Rated Peak Withstand Current | kA | 50/63 | |
5 | Rated Short-Circuit Closing Current | kA | 50/63 | |
6 | Short-Circuit Closing Operations | order | 30 | |
7 | Power Frequency Withstand Voltage: To Ground / Phase-to-Phase | kV | 42 | |
8 | Power Frequency Withstand Voltage: Across Breaker Contacts | kV | 48 | |
9 | Lightning Impulse Withstand Voltage: To Ground / Phase-to-Phase | kV | 75 | |
10 | Lightning Impulse Withstand Voltage: Open Contact | kV | 85 | |
11 | Main Circuit Resistance | μΩ | ≤60 | |
12 | Arc Extinguishing Chamber Mechanical Life | order | 10000 | |
13 | Isolating / Earthing Switch Mechanical Life | order | 5000 | |
14 | Gas Box Pressure | bar | 1.25 |