Isolating Mechanism-3

KENJING Isolation Operation Mechanism Under the Environmental Protection Cabinet

Compact switchgear operating mechanism for under-mounted environmental protection cabinets; 40 W, AC/DC 220/110/48/24, 2 kV/1 min dielectric, –40…+50 °C, 96 h salt-spray, with wide coil operating ranges for dependable isolation control.

The KENJING switchgear operating mechanism is a cabinet-mounted drive for isolators/earthing devices installed beneath sealed environmental cabinets. It supports AC/DC 220 V, AC/DC 110 V, DC 48 V, DC 24 V, delivers 40 W, passes 2 kV/1 min control-circuit dielectric tests, operates –40…+50 °C, and meets 96 h salt-spray resistance.

Key Features & Advantages

  • Wide control supply: AC/DC 220/110 and DC 48/24 let one switchgear operating mechanism cover new builds and retrofits.

  • Coil performance windows: Close coil 85–110% Un; open coil 65–110% Un for reliable actuation under utility voltage variation.

  • Low-voltage permissive: Functional threshold ≤30% Un aids safe release during LV testing and maintenance.

  • Dielectric robustness: Control circuit withstand 2 kV/1 min, supporting compact cabinet layouts.

  • Environmental durability: –40…+50 °C operation and 96 h salt-spray for coastal or industrial atmospheres.

  • Integration ready: The isolation switch operating mechanism includes interlock and position-feedback interfaces for SCADA/DAS.

Why Choose KENJING

  • Application fit: Purpose-built environmental protection cabinet mechanism with under-cabinet mounting, clear stroke/torque margins, and minimal alignment time.

  • Process control: Every switchgear operating mechanism is routine-tested for timing, latch force, and dielectric integrity.

  • Lifecycle support: Drawings, wiring schematics, retrofit brackets, and spares keep the switchgear operating mechanism maintainable over the asset life.

Specify the KENJING switchgear operating mechanism for under-cabinet isolation bays. Contact our engineers for interface drawings, commissioning guidance, and delivery options.

NO

ITEM

UNIT

PARAMETERS

REMARKS

1

Voltage Level

VAC/DC220;AC/DC110;DC48;DC24

2

Rated Power

W40

3

Operating Environment

+50-40

4

Power Frequency Withstand Voltage

kV2/1min

5

Closing Coil Normal Operating Voltage Range

UL85%~110%

6

Opening Coil Normal Operating Voltage Range

UL65%~110%

7

Low Voltage Operating Range

UL≤30%3

8

Salt Spray Resistance Level

h96

Isolation Operation Mechanism Under The Environmental Protection Cabinet (2)